MS100

Current Transformer Test Set

Current Transformer Test Set MS100 is a computer-controlled equipment set that performs fully automatic calibration of current transformers with primary current from 0.5 to 5000 A

    FEATURES AND BENEFITS

    • A complete set of equipment for Current Transformer testing
    • High accuracy (current error ± 0,005%; phase displacement ± 0,15 min)
    • Wide range of primary current: 0,5…5000 A
    • Rated secondary currents: 1 and 5 А
    • Rated power range: 5 to 50 V·A at cosφ = 0,8; 0,5 to 50 V·A at cosφ = 1
    • FS measurement function
    • Cable, contact and internal test set (Comparator) resistances are compensated by four-conductor connection
    • Measurement process controlled by PC
    • Automatic test reports generation using basic or user-created templates
    • High productivity

    APPLICATIONS

    MS100 is used by:

    • Manufacturers of Current and Voltage Transformers
    • On-site testing Current and Voltage  Transformers
    • Calibration laboratories
    • Metrology Institutes

    EQUIPMENT KIT

    M100Comparator
    S100Automatic Current Source
    M500Programmable Standard Current Transformer
    M500E1Range Extender
    M400Electronic Current Burden (rated current – 1 A)
    M401Electronic Current Burden (rated current – 5 A)

    OTHER OPTIONAL SUPPLIES


    Racks for stationary indoor using

     

    Trolleys for mobile on-site using

     

    CT Connection Device for acceleration the calibration  process

    TEST ARRANGEMENT

     

    Fig.1. Measuring circuit for primary rated current 0,5…600 А

    Fig. 2. Measuring circuit for primary rated current 650…5000 А

    Name

    Value

    Current error± 0,005 %
    Phase displacement± 0,15 min
    Current range1 … 150 %
    Rated primary current0,5; 0,6; 0,7; 0,75; 0,8; 0,9; 1; 1,25; 1,5; 2; 2,5; 3; 3,5; 4; 4,5; 5; 5,5; 6; 6,5; 7; 7,5; 8; 8,5;  9; 9,5; 10; 12,5; 15; 20; 25; 30; 35; 40; 45; 50; 55; 60; 65; 70; 75; 80; 85; 90; 95; 100; 105; 110; 115; 120; 125; 130; 135; 140; 145; 150; 155; 160; 165; 170; 175; 180; 185; 190; 195; 200; 225; 250; 275; 300; 325; 350; 375; 400; 425; 450; 475; 500; 525; 550; 575; 600; 650; 700; 750; 800; 850; 900; 950; 1000; 1050; 1100; 1150; 1200; 1250; 1300; 1350; 1400; 1450; 1500; 1550; 1600; 1650; 1700; 1750; 1800; 1850; 1900; 1950; 2000; 2100; 2200; 2250; 2300; 2400; 2500; 2600; 2700; 2750; 2800; 2900; 3000; 3100; 3200; 3300; 3400; 3500; 3600; 3700; 3800; 3900; 4000; 4100*; 4200*; 4300*; 4400*; 4500*; 4600*; 4700*; 4800*; 4900*; 5000* A
    Rated secondary current1; 5 A
    Rated power for cosφ = 0.80,5; 0,75; 1; 1,25; 1,5; 1,75; 1,875; 2; 2,5; 3; 3,75; 4; 5; 6,25; 7,5; 10; 11,25; 12,5; 15; 20; 25; 30; 40; 45*; 50* V·A
    Rated power for cosφ = 10; 0,5; 0,75; 0,8; 1; 1,25; 1,5; 1,875; 2; 2,5; 3,75; 4; 5; 6; 7,5; 10; 12,5; 15; 30; 50* V·A
    Output voltage (without a load)

     

    40 V  (at current range from 0,005 to 45 A)
    5 V  (at current range from 0,05 to 900 A)
    2 V (at current range from 0,1 to 6000)

    *Values are possible for 1 to 120 % of rated current

    EquipmentDimensions (W × H × D), mmWeight, kg
    M100 Comparator

    345 × 135 × 235

    5

    M400 Electronic Current Burden (rated current – 1 A)

    345 × 135 × 235

    5

    M401 Electronic Current Burden (rated current – 5 A)

    345 × 135 × 235

    5

    M500 Programmable Standard Current Transformer

    470 × 145 ×  375

    17

    M500E1 Range Extender

    110 × 350 × 210

    7

    S100.1

    Automatic Current Source

     

    S100SU

    450 × 200 × 430

    27

    S100PT1

    165 × 300 × 200

    17

    S100PT2

    165 × 300 × 200

    17

    S100PT3

    280 × 300 × 370

    29

    S100A1

    345 × 135 × 235

    8

     

    Power mains:
    Rated Voltage

    Rated Freguency

    220/230 V

    50 Hz

    Power consumption at the maximum load10 kV∙A
    Operating Temperature0 … 40 °С
    Relative Humidityup to 80 % non-condensing
    Standards

    Safety

    EMC

     

    EN 61010-1:2010

    EN 61326-1:2013

    Calibration Interval2 years recommended