M410

Electronic Voltage Burden

Electronic Voltage Burden M410 is used as a load in the secondary circuits of Voltage Transformers during their verification and calibration

    FEATURES AND BENEFITS

    • M410 sets burden power values for VT with rated secondary voltages 100/3, 100/√3, 100, 110/3, 110/√3, 110 V
    • Rated power range:
      1 to 10 V·A, cosφ = 1 at 50 Hz
      5 to 600 V·A, cosφ = 0,8 at 50 Hz
    • Sets 100 % and 25 % rated power
    • M410 can be integrated in a computer controlled test system in conjunction with Voltage Transformer Test Set M210/M211
    • Voltage overload protection
    • Wide range of emulated burden ratios
    • Small size and low weight

    APPLICATIONS

    M410 is used by:

    • Manufacturers of Current Transformers
    • On-site testing of Current Transformers
    • Calibration Laboratories
    • Metrology Institutes

    Rated voltage, V

    cosφ

    Rated burden power, VA

    100, 100/√3, 110, 110/√3

    0.8

    5; 10; 15; 20; 25; 30; 50; 60; 75; 100; 120; 150; 200; 300; 360; 400; 500; 600

    100, 100/√3, 100/3, 110, 110/√3,110/3

    1.0

    1, 2; 2.5; 3; 4, 5, 6, 7, 8, 9, 10

    100/3, 110/3

    0.8

    5; 10; 15; 20; 25; 30; 50; 60; 75; 100; 120; 150; 200

    Sets 100% and 25% rated burden power
    Active and reactive power errors± 0,03·S*
    Power mains:
    Rated voltage

    Rated freguency

    220/230 V

    50 Hz

    Operating Temperature0 … 40 °С
    Relative Humidityup to 80 % non-condensing
    Size345 × 135 × 235 mm
    Weight9 kg
    Standards

    Safety

    EMC

     

    EN 61010-1:2010

    EN 61326-1:2013

    Calibration Interval2 years recommended

    * – set burden power value